Hopp til hovedinnhold Hopp til søk Gå til hovednavigasjon

Fjernovervåking og IIoT

4G remote monitoring of unmanned sites: architecture and checklist

How to connect an unmanned site over 4G: outgoing connections or VPN, power, alarms, buffering when offline, and which ICP DAS devices fit.

4G remote monitoring of unmanned sites: architecture and checklist
Foto: USDAgov · Public domain · Wikimedia Commons

Pumping stations, reservoirs and machines at customer sites often have power but no wired network. A cellular link is then the practical way to get data out and alarms through. This article describes 4G remote monitoring of an unmanned site layer by layer: what runs on site, how to build the connection, how to handle power, alarms and lost connections, and which ICP DAS devices fit.

A 4G remote monitoring architecture in three layers

  • On site: I/O modules, meters and sensors, plus an edge controller that collects the values, runs local logic and handles communication.
  • Link: a 4G modem or router, built into the controller or installed separately, with a SIM card and an antenna.
  • Central: software that stores and displays the data and distributes alarms, such as SCADA, an MQTT broker with a database, or IoTstar.

Keep control decisions at the site. Stopping a pump on dry-running or starting a fan on high temperature should not depend on the mobile network. The cellular link is for reporting, supervision and maintenance access.

Build the connection from the site outwards

Most mobile subscriptions give the SIM a private IP address behind the operator's NAT. A central server cannot open a connection to the site, so the site has to connect out. Three patterns are common:

  • Push data from the site. The controller publishes to an MQTT broker or sends data to a server. This works with standard SIM cards. Use MQTT over TLS (port 8883) where the device supports it.
  • VPN tunnel. The site router or controller builds a tunnel to a central VPN server, and central systems reach the site through it. This is needed when SCADA polls Modbus TCP or engineers need the web interface for maintenance.
  • Private APN. Some operators offer private networks with fixed addresses. This ties the solution to one operator.

Do not expose Modbus TCP or a device web interface to the Internet through port forwarding. Modbus TCP has no authentication, so anyone who reaches the port can read and write values. Also consider data volume: polling every register once per second uses far more data than sending values on change or at a fixed interval.

Power, antenna and enclosure

Plan for mains failure. If the controller and router run from a DC supply with a battery buffer, the site can still report the failure and keep logging. Wire the mains-OK signal to a digital input so the outage itself becomes an alarm.

Mount the antenna outside metal cabinets and check signal quality at the actual installation point. Cabinets in direct sun get hot, so compare the operating temperature range of every component with the site conditions.

For solar-powered sites, the G-4510 power-saving PAC has a built-in solar charger for a 12 V lead-acid battery, low-voltage disconnect and an optional 4G modem module, with a stated deep-sleep consumption below 10 mA at 12 VDC. It is a programmable MiniOS7 controller rather than a browser-configured device.

Alarms and buffering when the link is down

Plan at least two alarm paths. Email and MQTT need a working data connection. SMS does not depend on a data session, which makes it a useful second path for critical alarms.

The central system should also detect silence: if a site has not reported within a set time, raise a communication alarm.

Log measurements locally with timestamps and send the logged data when the connection returns, so the central database has no gaps. Synchronise device clocks with SNTP so timestamps from different sites can be compared.

ICP DAS devices for 4G sites

Devices with built-in 4G for EMEA

WISE-5231M-4GE and WISE-2841M-4GE are edge controllers with a 4G modem specified for EMEA frequency bands (LTE FDD B1, B3, B5, B7, B8 and B20, plus 3G WCDMA). They run IF-THEN-ELSE rules, log data to a built-in 32 GB microSD card, publish over MQTT with SSL and send alarms by email and SMS. Both read RS-485 and Modbus TCP I/O modules, accept 12 to 48 VDC and operate from -25 to +75 °C. WISE-2841M-4GE adds VPN, HTTPS, SFTP/FTPS and SNMP v3.

PMC-5231M-4GE is a power meter concentrator with the same EMEA bands. It reads ICP DAS Modbus power meters, logs to microSD and sends back log files automatically when the network connection is restored.

GRP-540M-4GE is an Ethernet, serial and CAN to 4G gateway with router and port mapping functions and the LTE bands B1, B3, B5, B7, B8 and B20.

Ethernet devices behind an industrial 4G router

Any Ethernet-connected ICP DAS device can also be installed behind a standard industrial 4G router. UA series communication servers such as UA-5231M collect Modbus data, provide OPC UA and MQTT, include an OpenVPN client and recover remote database data after an offline period. ET-2200 I/O modules such as ET-2217 publish directly to an MQTT broker.

Central software and accessories

IoTstar runs on a Windows server or a virtual machine in a public cloud. It provides remote maintenance and firmware updates for WISE, PMC and PMD controllers, imports real-time and historical data into MS SQL, MySQL or Oracle, and offers dashboards with an alarm event list. External antennas such as ANT-421-05, a 4G LTE antenna with SMA connector, complete the installation.

Cellular variants and frequency bands differ by region, and several ICP DAS cellular models are sold only in specific markets. Check availability for your country with sales before you finalise the design.

Checklist before installation

  • Signal quality and operator coverage at the installation point
  • SIM type (public IP, private IP or private APN) and expected data volume
  • Connection pattern: push to a broker or server, or VPN for polling and maintenance
  • Logic that must keep running locally when the link is down
  • Alarm paths and a communication-loss alarm at the central system
  • Local logging and send-back after reconnection
  • Power supply, battery buffer and a mains-failure input
  • Cabinet temperature range and antenna position

Send us a description of your sites, signals and central system, and our technical sales team will propose a suitable setup.

Produkter for dette bruksområdet

PET-7017-10 CR
PET-7017-10 CR PET-7017-10 PoE Ethernet I/O Module, 10/20-ch Analog Input

The PET-7017-10 is a PoE-powered Ethernet analog input module for engineers who need voltage or current measurement on a networked I/O node. Its inputs can be set as 10 differential or 20 single-ended channels in software, and each channel can be given its own range, so one module can serve mixed sensor types on the same network.Each channel offers a choice of voltage ranges from ±150 mV to ±10 V and current ranges of ±20 mA, 0 ~ 20 mA and 4 ~ 20 mA, selected with jumpers. Resolution is 16-bit, and the module has two sampling modes: normal mode at 10 Hz total and fast mode at 50 Hz total. Open wire detection is available for 4 ~ 20 mA inputs, and differential channels are rated for 240 Vrms overvoltage protection.Configuration and monitoring are handled through a built-in web server with Web HMI, and the module supports Modbus TCP and Modbus UDP. Access is controlled by ID, password and IP filter. The unit is powered either from PoE (IEEE 802.3af, Class 1) or from a +12 ~ +48 VDC terminal block, and it mounts on a DIN rail.ApplicationsBuilding automationFactory automationMachine automationRemote maintenanceRemote diagnosisTesting equipment

Vanlig pris: 2 971,11 kr per stk. · mengderabatt fra 10 stk.
DN-AIH-08 CR
DN-AIH-08 CR DN-AIH-08 HART Analog Input Termination Board, 8-ch Active/Passive Loop

DN-AIH-08 is a termination board for HART analog input modules. It measures the analogue signal on each of its 8 channels and can also supply isolated loop power to field devices, so it accommodates both active and passive loop wiring.The board includes short-circuit protection on the isolated power output. If the circuit is shorted or the current becomes too high, the loop current is limited. Removable fuses protect loop devices from high inrush current, and each fuse has a physical indicator that shows when it has blown.Suited to HART analog input installations where field devices need to be wired in either active or passive loop configuration.Mounts on DIN-rail or wall, with dimensions of 135 x 214.6 x 25.5 mm.ApplicationsConnecting HART analogue field devices to HART analog input modulesLoop-powered field instrumentation requiring isolated passive loop powerIndustrial installations requiring protected analogue loop wiring

Vanlig pris: 3 947,63 kr per stk. · mengderabatt fra 10 stk.
DN-AII-08 CR
DN-AII-08 CR DN-AII-08 Current Input Termination Board, 8-ch Active/Passive Loop

DN-AII-08 CR is a termination board for current analog input modules. It connects field signals to the input channels and also measures the analog current, so it fits systems where the input is a current loop.The board supplies isolated loop power to field devices and supports both active and passive loop wiring on its 8 channels. The isolated supply is short-circuit protected: the loop current is limited when the circuit is shorted or the current becomes excessive. Removable fuses protect loop devices from high inrush current, and each fuse shows a physical indicator when it has blown.The board measures 135 x 214.6 x 25.5 mm and mounts on a DIN rail or on a wall. It is rated for an operating temperature of -25 ~ 75 °C and 5 ~ 95% RH, non-condensing.ApplicationsCurrent-loop field device wiring with active or passive loops

Vanlig pris: 3 417,82 kr per stk. · mengderabatt fra 10 stk.
DN-AIO-M CR
DN-AIO-M CR DN-AIO-M Universal Termination Board for Analog I/O

The DN-AIO-M CR is a universal termination board for analog input and output modules. It is designed as a general-purpose wiring point for most kinds of analog module, so one board can serve a range of analog I/O installations.Its footprint is small, matching other mini termination boards, which makes it easier to fit into control panels where space is limited. It can be mounted on a DIN rail or on a wall.Pin assignment and wiring information covers voltage and current input and output configurations.Operating range of -25 ~ 75 °C and 5 ~ 95% RH, non-condensing.Carries CE, UKCA, FCC, RoHS and WEEE markings.ApplicationsTerminating field wiring for analog input modulesTerminating field wiring for analog output modulesCompact wiring points in control panels and installations

Vanlig pris: 1 984,20 kr per stk. · mengderabatt fra 10 stk.

Mer om Fjernovervåking og IIoT

Trenger du hjelp til å velge?

Vi kjenner ICP DAS-sortimentet og hjelper deg med å finne riktig modul, tilbehør eller reservedel.

Kontakt teknisk salg

For bedriftskunder

  • Mengderabatt trekkes automatisk
  • Ingen dansk mva ved levering til Norge
  • Datablad og fullstendige spesifikasjoner for alle produkter
Opprett bedriftskonto