When new signals can bypass the PLC, when its program has to change, and which Ethernet I/O, fieldbus I/O and gateways fit each case.

Adding I/O to an existing PLC without changing the program
Foto: AJ Yorio · CC0 · Wikimedia Commons

A machine that has run for years often needs a few more signals: motor temperatures for maintenance, a cycle counter for OEE, or a sensor for a new process step. Changing the PLC program needs the original project, someone who knows the code, a production stop and sometimes a new acceptance test. This article explains how to add I/O to an existing PLC system, when the program can stay as it is, and when a change cannot be avoided.

Start with who uses the signal

The deciding question is who needs the value. If only people and IT systems use it, for dashboards, logs or maintenance alarms, the PLC does not have to see it, and the new I/O can be read by SCADA or an edge device.

If the value must affect the machine, as an interlock, a start permissive or a setpoint, the PLC logic has to use it, and the aim is to keep that change small. Safety functions belong in the machine's safety circuit and are outside the scope of this article.

Four ways to add I/O to an existing PLC

1. Parallel Ethernet I/O read by SCADA or an edge device

An Ethernet I/O module is wired to the new sensors and connected to the plant network rather than to the PLC. SCADA reads it over Modbus TCP. The ET-2200 series can also publish values over MQTT, and OPC UA I/O modules such as the U-7560M have OPC UA, MQTT and a RESTful API built in. The PLC program and hardware configuration stay untouched.

If the data has to reach an MES or a cloud platform, a UA-5231M communication server reads Modbus TCP and RTU devices and converts the values to OPC UA, MQTT or SNMP. For simple local logic, a WISE-5231M edge controller runs IF-THEN-ELSE rules set up in a web browser and connects to up to 16 Modbus TCP modules and up to 32 DCON or Modbus RTU modules.

2. Fieldbus slave I/O on the PLC's own network

If the PLC needs the signal, the direct route is an I/O module on the PLC's fieldbus. ICP DAS has slave I/O for PROFINET (PFN-2000, with a GSDML file), PROFIBUS DP (PROFI-5000, with a GSD file), EtherNet/IP (EIP-2000, with two ports for daisy-chaining) and CANopen (CAN-2000C, with an EDS file). The module is added to the PLC's hardware configuration with its device file.

That is a configuration change, and on most PLCs it means a download. The logic only changes if the new values are used in it.

3. A gateway to Modbus I/O

When Modbus I/O is already installed, or suits the signals or distances better, a gateway maps Modbus data into the PLC's fieldbus. The GW-7662 lets a PROFINET controller access Modbus RTU/ASCII devices such as M-7000 modules, and the GW-7663 does the same for Modbus TCP devices such as ET-7000 modules. The GW-7553 gives a PROFIBUS master access to Modbus TCP devices, the GW-7472 links an EtherNet/IP scanner to Modbus RTU and TCP devices, and the I-7232D connects up to 10 Modbus RTU I/O modules to a CANopen master.

To the PLC the gateway is one fieldbus device, so the same rule applies.

4. Modbus TCP I/O polled by the PLC

Many PLCs can act as a Modbus TCP client and read any Modbus TCP module directly. The polling has to be set up in the PLC, so this route always involves the PLC project.

When the PLC program must change

RequirementPLC program changeTypical route
Trend, log or report a valueNoEthernet I/O read by SCADA (1)
Maintenance alarms or e-mail messagesNoEdge controller or communication server (1)
Show the value on the PLC's HMIUsually, unless the HMI can read the module over Modbus TCP(1) or (2)
Use the value in an interlock, sequence or control loopYesFieldbus slave I/O or gateway (2, 3)
Switch a non-critical output from SCADA, such as a warning lightNo, but agree which system owns the outputEthernet I/O with digital outputs (1)

Worked example: two requirements, two routes

A filling machine is controlled by a PROFINET PLC. Maintenance wants eight bearing and motor temperatures with trends, and production wants the machine to stay stopped until a newly installed chiller reports ready.

  • The temperatures are for people, not for the control logic. An ET-2215H with eight RTD inputs, 3-wire lead resistance compensation and open-wire detection is connected to the plant network. SCADA polls it over Modbus TCP, and the PLC is not touched.
  • The chiller signal is a start permissive, so the PLC must see it. A PFN-2051 with 16 isolated digital inputs is added to the PROFINET network with its GSDML file, and one condition is added to the start logic.

The result is one small program change with a clear test.

Practical checks before installation

  • Keep parallel Ethernet I/O on the plant or SCADA network, away from the PLC's real-time fieldbus traffic where possible.
  • Plan IP addresses and restrict access. The ET-2200 series supports a password and an IP filter.
  • Define power-on and safe values for outputs so they go to a known state if communication is lost. The ET-2242, for example, supports both, plus a dual watchdog.
  • Check isolation between field wiring and network. The ET-2200 modules mentioned here have 3000 VDC I/O isolation.
  • Fuse the module supply separately and update the wiring diagrams.

Which ICP DAS product groups fit

  • Ethernet I/O modules (ET-2200, ET-7200, OPC UA I/O) for parallel monitoring without PLC changes.
  • Fieldbus I/O modules (PFN-2000, PROFI-5000, EIP-2000, CAN-2000C) when the PLC must read the signal.
  • Fieldbus gateways (GW-7662, GW-7663, GW-7553, GW-7472, I-7232D) to bring Modbus I/O into the PLC's network.
  • IIoT communication servers and edge controllers (UA-5231M, WISE-5231M) to pass data to MES or cloud platforms.

Send technical sales the PLC type, its fieldbus and your signal list, and we will suggest the route and modules that fit.

Produkter for dette bruksområdet

PET-7017-10 CR
PET-7017-10 CR PET-7017-10 PoE Ethernet I/O Module, 10/20-ch Analog Input

The PET-7017-10 is a PoE-powered Ethernet analog input module for engineers who need voltage or current measurement on a networked I/O node. Its inputs can be set as 10 differential or 20 single-ended channels in software, and each channel can be given its own range, so one module can serve mixed sensor types on the same network.Each channel offers a choice of voltage ranges from ±150 mV to ±10 V and current ranges of ±20 mA, 0 ~ 20 mA and 4 ~ 20 mA, selected with jumpers. Resolution is 16-bit, and the module has two sampling modes: normal mode at 10 Hz total and fast mode at 50 Hz total. Open wire detection is available for 4 ~ 20 mA inputs, and differential channels are rated for 240 Vrms overvoltage protection.Configuration and monitoring are handled through a built-in web server with Web HMI, and the module supports Modbus TCP and Modbus UDP. Access is controlled by ID, password and IP filter. The unit is powered either from PoE (IEEE 802.3af, Class 1) or from a +12 ~ +48 VDC terminal block, and it mounts on a DIN rail.ApplicationsBuilding automationFactory automationMachine automationRemote maintenanceRemote diagnosisTesting equipment

Vanlig pris: 2 971,11 kr per stk. · mengderabatt fra 10 stk.
BNET-2310M CR
BNET-2310M CR BNET-2310M BACnet/IP I/O Module, 4-ch AI, 2-ch AO, 4-ch DI, 4-ch DO

The BNET-2310M CR is a remote I/O module that brings 4 analogue inputs, 2 analogue outputs, 4 digital inputs and 4 digital outputs onto a BACnet/IP network. A BMS or BACnet/IP client can read field sensor signals directly over Ethernet and command connected analogue or digital output devices, without a separate gateway.The module operates as a BACnet/IP Server and also supports Foreign Device functionality. It can register with a specified BBMD to receive BACnet/IP messages forwarded across different IP subnets, which suits multi-floor buildings, multi-building facilities, industrial sites and larger BEMS installations.Configuration is handled through a built-in web server, so the module can be set up from a standard web browser. Configuration files can be imported and exported for backup and repeat deployments. The CR ordering code is the RoHS-marked variant.ApplicationsHVAC control and monitoring in building automationLighting and energy managementBMS and BEMS integration via BACnet/IPMulti-floor buildings and multi-building facilitiesIndustrial sites with BACnet/IP field I/O

Vanlig pris: 2 815,28 kr per stk. · mengderabatt fra 10 stk.
CAN-2012C CR
CAN-2012C CR CAN-2012C CANopen Slave Module, 16-bit 16-ch Analog Input

The CAN-2012C is a CANopen slave analog input module that brings 16-bit measurements onto a CAN bus network. It provides 8 differential or 16 single-ended inputs, selectable in software, and covers voltage ranges of ±10V, ±5V, ±2.5V and 0~10V as well as current ranges of ±20mA, 0~20mA and 4~20mA. Each channel can be configured individually.Built for CANopen networks, the module follows CiA 301 v4.02 and CiA 401 v2.1 and operates as an NMT slave with Node Guarding and Heartbeat error control. A default EDS file is provided for use with standard CANopen master software, and the module has passed the CiA CANopen conformance test tool, which simplifies commissioning with masters from ICP DAS or other manufacturers.Electrical features include 4 kV contact ESD protection on each channel, support for a 10 to 30 VDC supply, and isolation rated at 2500 Vrms for photo-coupling and 3000 VDC for DC-to-DC. The module mounts on DIN-rail and operates from -25 to +75 °C.ApplicationsIndustrial machinery controlFactory automationPackaging machine controlRemote data acquisitionEnvironmental monitoringVehicle control systemsMedical equipment control

Vanlig pris: 3 199,66 kr per stk. · mengderabatt fra 10 stk.
CAN-2015C CR
CAN-2015C CR CAN-2015C CANopen Slave Module, 8-ch RTD Input

The CAN-2015C CR connects eight RTD sensors to a CANopen network as a slave device. Each channel accepts 2-wire or 3-wire RTD sensors, with 16-bit resolution and an accuracy of +/-0.05% FSR. Engineers can read RTD values or configure the module over standard CANopen messaging.The module follows CiA 301 v4.02 and CiA 401 v2.1 and has passed validation with the CiA CANopen Conformance Test tool. A default EDS file is provided, so it can be added to a standard CANopen master with minimal configuration effort. It also works with the CANopen masters offered by ICP DAS.Diagnostic and protection features include open wire detection, individual channel configuration, a built-in 120Ω terminal resistor and 4 kV contact ESD protection on each channel. The unit runs from +10 ~ +30 VDC and is intended for DIN-rail mounting, with an operating range of -25 ~ +75 °C.ApplicationsIndustrial machine controlFactory automationPackaging machine controlRemote data acquisitionEnvironmental monitoringVehicle control systemsMedical equipment control

Vanlig pris: 3 563,26 kr per stk. · mengderabatt fra 10 stk.

Mer om Fabrikk- og maskinautomasjon

Trenger du hjelp til å velge?

Vi kjenner ICP DAS-sortimentet og hjelper deg med å finne riktig modul, tilbehør eller reservedel.

Kontakt teknisk salg

For bedriftskunder

  • Mengderabatt trekkes automatisk
  • Ingen dansk mva ved levering til Norge
  • Datablad og fullstendige spesifikasjoner for alle produkter
Opprett bedriftskonto