Temperature sensors for building automation: RTD, NTC or 0–10 V

Pt100, Pt1000, NTC thermistor or 0–10 V transmitter: wiring, cable length, accuracy and which ICP DAS input modules read each sensor type.

Temperature sensors for building automation: RTD, NTC or 0–10 V
Foto: Erol Ahmed · CC0 · Wikimedia Commons

Temperature is the most common measurement in a building, from water circuits to duct, room and outdoor air. Choosing temperature sensors for building automation is mostly a choice between Pt100 and Pt1000 resistance thermometers, NTC thermistors and transmitters with a 0–10 V or 4–20 mA output. That choice decides which input module you need, how far the sensor can be from it and how accurate the reading will be. Below we compare the options, calculate the effect of cable resistance and list which ICP DAS input modules read each sensor type.

The sensor types

Pt100 and Pt1000

Platinum resistance thermometers (RTDs) follow a standard curve defined in IEC 60751. A Pt100 has 100 Ω at 0 °C and a Pt1000 has 1000 Ω. With the standard coefficient, resistance rises by about 0.385 Ω per kelvin for a Pt100 and 3.85 Ω per kelvin for a Pt1000. Sensors from different manufacturers are interchangeable within their tolerance class, which makes RTDs the usual choice for water circuits and energy calculations.

NTC thermistors

The resistance of an NTC thermistor falls as temperature rises, and the change per kelvin is large, so lead resistance hardly matters. The curve is non-linear and differs between types: a 10 kΩ NTC from one manufacturer does not necessarily match a 10 kΩ NTC from another. The input module must use the exact curve, or readings can be several degrees off at the ends of the range.

0–10 V and 4–20 mA transmitters

A transmitter combines a sensor element with electronics that convert temperature into a standard signal over a fixed range, for example 0–50 °C. It needs a supply, usually 24 V, but any analog input can read it. Voltage signals are sensitive to voltage drop and interference on long cables. A 4–20 mA loop is more robust over distance, and a current below 4 mA shows a broken wire.

2-wire, 3-wire and 4-wire RTD connections

With a 2-wire connection the input measures the sensor plus the resistance of both conductors. A 3-wire connection adds a third conductor so that the module can measure the lead resistance and subtract it, assuming equal conductors. A 4-wire connection separates the measuring current from the voltage sensing and removes the lead resistance almost completely.

Worked example: a copper conductor of 0.5 mm² has about 0.035 Ω per metre at 20 °C. In a 2-wire circuit both conductors add to the reading:

Cable length (one way)Loop resistanceError with Pt100Error with Pt1000
10 m0.7 Ω+1.8 K+0.18 K
25 m1.75 Ω+4.5 K+0.45 K
50 m3.5 Ω+9.1 K+0.91 K

A 2-wire Pt100 is therefore only acceptable with very short leads. A 2-wire Pt1000 is often good enough for room and duct sensors. For long runs, and for water temperatures that feed energy calculations, use 3-wire or 4-wire connections. Lead resistance also varies with cable temperature, so a fixed offset correction is never exact.

Accuracy: sensor, cable and input module

The total error is the sum of the sensor tolerance, the wiring effect and the input module. IEC 60751 class B allows ±(0.3 + 0.005·|t|) °C, which is ±0.4 °C at 20 °C, and class A allows ±(0.15 + 0.002·|t|) °C. Input module accuracy is usually stated as a percentage of the full-scale range (FSR), so convert it using the temperature span of the selected input type. Use twisted, shielded cable, keep sensor cables away from mains and motor cables, and earth the shield at one end only.

Comparison of temperature sensors for building automation

SensorTypical use in buildingsCable lengthInterchangeableNeeds supply
Pt100Water circuits, plant roomsShort in 2-wire, long in 3- or 4-wireYes, within tolerance classNo
Pt1000Room, duct, outdoor, pipesMedium in 2-wire, long in 3-wireYes, within tolerance classNo
NTC thermistorRoom units, HVAC equipmentLong, little lead effectOnly with the same curveNo
0–10 V / 4–20 mATransmitters, mixed signal listsLong with 4–20 mAYes, by rangeYes

Which ICP DAS input modules read which sensors

RS-485 modules with Modbus RTU

  • M-7015-G: 6 RTD inputs for Pt100, Pt1000, Ni120, Cu50, Cu100 and Cu1000, configurable per channel, with open wire detection.
  • M-7015P-G: the same 6 inputs with lead resistance elimination for 3-wire connections, designed for long-distance RTD measurement.
  • M-7033-G: 3 RTD inputs for Pt100, Pt1000 and Ni120 in 2-, 3- or 4-wire connection, with lead resistance elimination in 3- and 4-wire mode.
  • M-7005-G: 8 thermistor inputs with predefined types and user-defined types entered as Steinhart coefficients, plus 6 alarm outputs.
  • tM-TH8: 8 isolated thermistor inputs, also with user-defined types.
  • M-7017R-G: 8 differential inputs for voltage up to ±10 V and for current; current inputs need an external 125 Ω resistor.

Ethernet modules with Modbus TCP

  • ET-7015 and PET-7015: 7 RTD inputs for Pt100, Pt1000, Ni120, Cu100 and Cu1000 in 2- or 3-wire connection, with 3-wire lead resistance elimination. PET-7015 adds PoE to IEEE 802.3af.
  • PET-7215: the same RTD inputs with a 2-port Ethernet switch for daisy-chain wiring.
  • PET-7005: 8 thermistor inputs with user-defined types and 4 digital outputs.
  • PET-7017: 8 jumper-selectable voltage or current inputs for transmitters.

Other options

If the BMS uses BACnet/IP, the BNET-2310M reads 0–10 V transmitters directly on its ±10 V analog inputs. If a controller only has voltage or current inputs, the SG-3013-G signal conditioner converts one Pt100, Pt1000 or Ni120 sensor into 0–10 V or 4–20 mA. For room climate, the DL-10 reports temperature (typically ±0.4 °C), humidity and dew point over Modbus RTU.

Checklist before you choose

  • Sensor type and exact curve: Pt100 or Pt1000 coefficient, NTC type or its Steinhart coefficients
  • Connection type (2-, 3- or 4-wire) and the longest cable run
  • Required accuracy at the operating point, including the sensor tolerance class
  • Points per location and the available network: RS-485, Ethernet or PoE
  • Protocol on the BMS side: Modbus RTU, Modbus TCP or BACnet

Send your sensor list and cable lengths to our technical sales team for a module proposal.

Produkter for dette bruksområdet

PET-7017-10 CR
PET-7017-10 CR PET-7017-10 PoE Ethernet I/O Module, 10/20-ch Analog Input

The PET-7017-10 is a PoE-powered Ethernet analog input module for engineers who need voltage or current measurement on a networked I/O node. Its inputs can be set as 10 differential or 20 single-ended channels in software, and each channel can be given its own range, so one module can serve mixed sensor types on the same network.Each channel offers a choice of voltage ranges from ±150 mV to ±10 V and current ranges of ±20 mA, 0 ~ 20 mA and 4 ~ 20 mA, selected with jumpers. Resolution is 16-bit, and the module has two sampling modes: normal mode at 10 Hz total and fast mode at 50 Hz total. Open wire detection is available for 4 ~ 20 mA inputs, and differential channels are rated for 240 Vrms overvoltage protection.Configuration and monitoring are handled through a built-in web server with Web HMI, and the module supports Modbus TCP and Modbus UDP. Access is controlled by ID, password and IP filter. The unit is powered either from PoE (IEEE 802.3af, Class 1) or from a +12 ~ +48 VDC terminal block, and it mounts on a DIN rail.ApplicationsBuilding automationFactory automationMachine automationRemote maintenanceRemote diagnosisTesting equipment

Vanlig pris: 2 971,11 kr per stk. · mengderabatt fra 10 stk.
AR-200 CR
AR-200 CR AR-200 Accelerometer Data Logger, 2-ch IEPE Input

AR-200 CR is a dynamic signal acquisition module for vibration monitoring and analysis. It accepts two IEPE accelerometers, each supplied with a built-in 3 mA excitation current, and digitises the signals with a 16-bit converter. Sampling of both channels runs simultaneously, at rates up to 200 kHz per channel.Recordings are written to a Micro SD card, so data can be taken away and analysed offline. Capture can be started by a push button, a schedule, an analog threshold, a digital input or a remote command from the supplied utility on a host PC, which also lets you set the sampling rate and scheduling for each application. A single relay output and one digital input add basic event handling to the unit.The logger suits panel or machine installations that need to run unattended. It works from a wide +10 to +30 VDC supply, operates from -25 to +75 °C, and provides 4 kV contact ESD protection on all terminals. Mounting is by wall or DIN-rail.ApplicationsVibration monitoring and analysisIndustrial automationFactory automationProcess automation

Vanlig pris: 6 233,10 kr per stk. · mengderabatt fra 10 stk.
AR-400 CR
AR-400 CR AR-400 Accelerometer Data Logger, 4-ch IEPE Input

The AR-400 is a dynamic signal acquisition module for vibration monitoring and analysis. It samples four channels simultaneously with 16-bit resolution and supplies a built-in 3 mA excitation current for IEPE accelerometers, so compatible sensors can be connected directly without an external supply.Acquired data is written to a micro SDHC card (4 to 32 GB), allowing offline analysis after capture. Recording can be started by push button, schedule, analog threshold, digital input or remote trigger from the utility software installed on a host PC, which also handles sample rate and sampling schedule settings.Suited to condition monitoring setups where vibration data must be captured at defined times or on defined events.Includes a relay output (Form A, 5A@250 VAC) and a digital input for use within trigger or control logic.ApplicationsVibration monitoring and analysisIndustrial automationFactory automationProcess automation

Vanlig pris: 7 116,12 kr per stk. · mengderabatt fra 10 stk.
CL-202-E CR
CL-202-E CR CL-202-E CO2/Temperature/Humidity Data Logger, RS-485 and Ethernet PoE

CL-202-E CR is a data logger module for monitoring indoor air quality and climate conditions. It measures CO2 with a non-dispersive infrared (NDIR) sensor, alongside temperature, relative humidity and dew point, and records the results with date and time stamps for later analysis.The module offers an RS-485 port and an Ethernet port with PoE support, so it can be integrated into existing HMI or SCADA systems over DCON, Modbus RTU, Modbus TCP or MQTT. Real-time readings can be viewed from the iAir Utility, the iOS or Android apps, or a web browser, provided the logger is on the same local network. Logged data can be exported to CSV for analysis in standard spreadsheet or industry software.Relay output for alarm signalling or control of IAQ equipmentCeiling or wall mounting, IP20 housing, Ø 150 x 53 mmOperating temperature 0 ~ 50°C, non-condensing humidity range 10 ~ 90% RHApplicationsTransportation of food or pharmaceuticalsFood and beverage industry (HACCP)Blood stations and pharmaciesBuilding and energy managementWarehouse managementMuseums, archives and galleriesIndoor or underground parking lot air quality monitoring

Vanlig pris: 4 124,23 kr per stk. · mengderabatt fra 10 stk.

Mer om Bygningsautomasjon