Hopp til hovedinnhold Hopp til søk Gå til hovednavigasjon

iSN-101 Liquid Leak Detection Module, 1-ch with Modbus RTU and DCON

Produktinformasjon "iSN-101 Liquid Leak Detection Module, 1-ch with Modbus RTU and DCON"

The iSN-101 CR is a wall-mount liquid leak detector that switches its own relay output when water is detected, so it can drive a local alarm or signal a building or monitoring system without an external converter.

It accepts either a point probe for spot monitoring or a line sense cable for longer runs, with total cable length of up to 500 m. Sensitivity is set with a rotary switch, and the module includes a buzzer with a push button to silence it. Cable-break detection is available when used with the CA-LLD-DC100X-Lxxx sense cable.

Communication is via a single RS-485 port that supports Modbus RTU or DCON, with software-configurable baud rates from 1200 to 115200 bps. For Modbus RTU networks, the device address can be set in hardware, and the module can be paired with the WISE IoT Edge Controller or TPD/VPD Touch HMI.

Applications

  • Water pipe leak monitoring in buildings, including water, fire and sewage pipes
  • Real-time leak detection in computer rooms, base stations, warehouses, libraries and museums
  • Monitoring air handling equipment, refrigeration units, liquid containers and pump tanks
  • Industrial sites where equipment leakage must be detected and alarmed remotely
Product type: Liquid leak detection module
Interface: RS-485
Protocol: DCON, Modbus RTU
Ports: 1
Power input: 10 ~ 30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: Wall mount

Spesifikasjoner

EMS Protection
EFT (IEC 61000-4-4)±4 kV for Power
ESD (IEC 61000-4-2)±8 kV Air for Random Point
LED Indicators
Status1 as Power Indicator
1 as Alarm Indicator
System
AlarmFor both liquid leak detection and cable-break detection.
BuzzerYes.
Can be muted by a push button.
Relay OutputSignal Relay, Form A x1, SPST
0.25 A @ 250 VAC
0.5 A @ 125 VAC
2 A @ 30 VDC
Liquid Leak Detection
Channels1
Liquid TypeWater, 2uS/cm
Sensor TypeProbe for point detection
or Cable for line detection
Max. Cable Length500 meters
Include Liquid Leak Detection Cable and Extended Cables.
Sensitivity Range26 KΩ ~ 580 KΩ (adjustable by rotary switch)
Cable-break DetectionYes.
For sense cable CA-LLD-DC100X-Lxxx only.
COM Ports
Ports1 x RS-485
Baud RateSoftware Configuration: 1200 ~ 115200 bps
Data Format(N,8,1), (O,8,1), (E,8,1), (N,8,2)
ProtocolModbus RTU or DCON
Power
Reverse Polarity ProtectionYes
Input Range10 ~ 30 VDC
Consumption1.5 W Max.
Mechanical
Dimensions (mm)80 x 70 x 28 (W x L x H)
InstallationWall mount
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +80°C
Humidity10 ~ 90% RH, Non-condensing

Spesifikasjoner som oppgitt av produsenten. Med forbehold om endringer.

0 av 0 vurderinger

Gjennomsnittlig vurdering av 0 av 5 stjerner

Legg igjen en anmeldelse!

Del dine erfaringer med andre kunder.