ZT-2015 ZigBee Wireless 6-ch RTD Input Module, Router

Produktinformasjon "ZT-2015 ZigBee Wireless 6-ch RTD Input Module, Router"

The ZT-2015 CR is a wireless RTD acquisition node that lets engineers collect temperature readings from six channels without running signal cabling back to a controller. It operates in the ISM 2.4 GHz band and acts as a ZigBee router, so it can extend a wireless network while it reports its own measurements.

Each channel accepts 2-wire or 3-wire RTD sensors and can be configured individually. The 3-wire lead resistance elimination keeps readings accurate over long cable runs, and open wire detection and overvoltage protection (120 VDC/110 VAC) help protect the module and flag faulty connections. Address, protocol, checksum, ZB-PID, ZB-channel and type code are set with rotary and DIP switches, and a Windows GUI configuration utility is available.

With a stated line-of-sight range of 300 m to 700 m, depending on the RF power setting, and 3000 VDC intra-module isolation, the ZT-2015 CR suits distributed temperature monitoring in building, factory and machine automation, as well as remote maintenance and diagnosis tasks.

Applications

  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
Product type: Wireless I/O Module
Interface: ZigBee
Protocol: DCON, Modbus RTU
Analog inputs: 6
Isolation: 3000 VDC
Power input: +10 ~ +30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail

Spesifikasjoner

CPU Module
Watchdog TimerYes, Module (1.6 Seconds), Communication (Programmable)
Isolation
Intra-module Isolation3000 VDC
EMS Protection
EFT (IEC 61000-4-4)±4 kV for Power Line
ESD (IEC 61000-4-2)±4 kV Contact for Power Line, Communication Line and each Channel,
±8 kV Air for Random Point
Surge (IEC 61000-4-5)±3 kV for Power Line
LED Indicators
Status1 x Power and Communication
ZigBee
Antenna2.4 GHz - 5 dBi Omni directional
Max. Slaves255
ProtocolSupports DCON and Modbus RTU Protocols
StandardZigBee PRO 2007
Transmission Power10 dBm to 19 dBm (EIRP) (Adjustable via Utility)
Transmission Distance (LoS)300 m to 700 m (Depending on the RF power setting)
Analog Input
Channels6
Type2/3-wire RTD
Sensor TypePt100, Pt1000, Ni120, Cu100, Cu1000
Sampling Rate12 Samples/Sec. (Total)
Common Mode Rejection150 dB
Normal Mode Rejection100 dB
Overvoltage Protection120 VDC/110 VAC
Individual Channel ConfigurationYes
Open Wire DetectionYes
3-wire RTD Lead Resistance EliminationYes
Analog Output
Accuracy±0.05%
Power
Input Range+10 VDC ~ +30 VDC
Consumption1.5 W Max.
Mechanical
Dimensions (mm)33 x 87 x 110 (W x L x H)
InstallationDIN-Rail
Environment
Operating Temperature-25 ~ +75°C
Storage Temperature-30 ~ +80°C
Humidity10 ~ 90% RH, Non-condensing

Spesifikasjoner som oppgitt av produsenten. Med forbehold om endringer.