ZT-2053-IOG ZigBee I/O Pair-connection Coordinator, 14-ch Isolated DI
ZigBee coordinator module with 14 isolated digital inputs that manages multi-to-multi I/O pair-connection across a wireless network. Accepts dry and wet contacts and mounts on DIN-rail.
- 14 isolated digital inputs supporting dry and wet contact signals, with 3750 VDC intra-module isolation
- Operates as ZigBee Coordinator, processing input events and distributing output states for the pair-connection network
- Supports 280 logical pair-connection channels and up to 255 slaves
- ZigBee 2007 Pro on the 2.4 GHz ISM band, fully compliant with IEEE 802.15.4/ZigBee specifications
- AES-128 encryption for wireless communication
- Adjustable RF output power from 10 dBm to 19 dBm (EIRP), giving 300 m to 700 m line-of-sight range depending on setting
2 233,53 kr per stk.
| 1–9 stk. | 2 233,53 kr | |
|---|---|---|
| 10–30 stk. | 2 160,81 kr | −3 % |
| 31+ stk. | 2 119,25 kr | −5 % |
Produktinformasjon "ZT-2053-IOG ZigBee I/O Pair-connection Coordinator, 14-ch Isolated DI"
ZT-2053-IOG CR is a ZigBee I/O module configured as the coordinator of an IOG pair-connection network. It monitors 14 isolated digital inputs and handles the logic that decides which remote outputs should change state, so that inputs on one module can drive outputs on others without wiring between them.
Any change of state on a digital input is reported immediately to the coordinator, which evaluates the I/O mapping and returns the resulting output states. The coordinator then sends periodic broadcasts to the ZT-IOG router modules so that their outputs stay synchronised with the network.
- Suited to distributed input monitoring over 2.4 GHz ZigBee links with AES-128 encryption.
- Pair-connection mapping is configurable, so the relationships between inputs and outputs can be adjusted to suit the installation.
Applications
- Wireless distributed digital input monitoring
- Multi-to-multi I/O pair-connection between remote ZT-IOG modules
| Product type: | Wireless I/O Module |
|---|---|
| Interface: | ZigBee |
| Protocol: | ZigBee 2007 Pro |
| Digital inputs: | 14 |
| Isolation: | 3750 VDC |
| Power input: | +10 VDC ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Spesifikasjoner
| Isolation | |
|---|---|
| Intra-module Isolation | 3750 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | 4 kV for Power Line |
| ESD (IEC 61000-4-2) | 4 kV Contact for Power Line, Communication Line and each Channel, 8 kV Air for Random Point |
| Surge (IEC 61000-4-5) | 3 kV for Power |
| LED Indicators | |
| Status | 1 x Power/Debug 1 x Communication 14x Digital Input |
| ZigBee | |
| Antenna | 2.4 GHz, 5 Omni-Directional |
| Max. Slaves | 255 |
| Standard | ZigBee 2007 Pro |
| Transmission Power | 10 dBm to 19 dBm (EIRP) (Adjustable via Utility) |
| Transmission Distance (LoS) | 300 m to 700 m (Depending on the RF power setting) |
| Digital Input | |
| Channels | 14 |
| Type | Dry + Wet Contact |
| ON Voltage Level | Dry: Close to GND Wet: +3.5 VDC ~ +30 VDC |
| OFF Voltage Level | Dry: Open Wet: Max. +1 VDC |
| Input Impedance | 3 kΩ, 0.33 W |
| Effective Distance | 500 M Max. |
| Power | |
| Input Range | +10 VDC ~ +30 VDC |
| Consumption | Max. 0.72 W |
| Mechanical | |
| Dimensions (mm) | 33 x 87 x 110 (W x L x H) |
| Installation | DIN-Rail |
| Environment | |
| Operating Temperature | -25 ~ +75°C |
| Storage Temperature | -30 °C ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Spesifikasjoner som oppgitt av produsenten. Med forbehold om endringer.