PM-3112-100P-CPS Single-Phase Power Meter, CANopen, 2 Loops, 60 A CT
CANopen single-phase power meter with two measurement loops, true RMS readings and clip-on 60 A CTs (10 mm aperture, 4 m lead) for energy monitoring.
- True RMS measurement of voltage, current, active, apparent and reactive power, energy, power factor and frequency
- Two independent single-phase loops (1P2W-1CT wiring) with separate reference voltages
- Clip-on 60 A CT with 10 mm aperture and 4 m wire lead, for fast installation on existing cables
- Power accuracy better than 0.5% (PF=1) with a 1 second data update rate
- CANopen communication with DIP switch selectable baud rate: 125 k (default), 250 k, 500 k, 1 M
- Two Form A power relay outputs, 5 A @ 250 VAC / 30 VDC, for alarm signalling
2 410,13 kr per stk.
| 1–9 stk. | 2 410,13 kr | |
|---|---|---|
| 10–30 stk. | 2 337,41 kr | −3 % |
| 31+ stk. | 2 285,47 kr | −5 % |
Produktinformasjon "PM-3112-100P-CPS Single-Phase Power Meter, CANopen, 2 Loops, 60 A CT"
PM-3112-100P-CPS CR is a two-loop, single-phase power meter with a CANopen interface, suited to engineers who need real-time electrical data from a DIN-rail mounted device. Each loop uses a clip-on 60 A current transformer with a 10 mm aperture and a 4 m wire lead, so the unit can be fitted to existing conductors without disconnecting the load.
The meter reports true RMS voltage and current, active, apparent and reactive power, the corresponding energy values, power factor and frequency, updated every second. Power accuracy is better than 0.5% at PF=1, and the measurement input accepts 10 ~ 300 V at 50/60 Hz, with current range 0.05 A ~ 60 A for this CT.
Communication runs over CANopen at 125 k (default), 250 k, 500 k or 1 M, selectable by DIP switch. Two Form A power relay outputs rated 5 A @ 250 VAC or 30 VDC can drive sirens or indicator lights for alarm messages. The plastic housing measures 33 x 127 x 100 mm (W x L x H) and operates from -20 ~ +70 °C.
Applications
- Generator monitoring
- Switchgear distribution systems
- Energy management
| Product type: | Power meter |
|---|---|
| Interface: | CANopen |
| Protocol: | CANopen |
| Relay outputs: | 2 |
| Power input: | +12 ~ 48 VDC |
| Operating temperature: | -20 ~ +70 °C |
| Mounting: | DIN-rail |
| Housing: | Plastic |
Spesifikasjoner
| AC Power Measurement | |
|---|---|
| Wiring | 1P2W-1CT |
| Loops | 1-phase: 2 |
| Input Voltage | 10 ~ 300 V |
| Input Current | PM-3112-100-CPS: CTØ10 mm (0.05 A ~ 60 A) PM-3112-100P-CPS: CTØ10 mm (0.05 A ~ 60 A) PM-3112-160-CPS: CTØ16 mm (0.1 A ~ 100 A) PM-3112-160P-CPS: CTØ16 mm (0.1 A ~ 100 A) PM-3112-240-CPS: CTØ24 mm (0.15 A ~ 200 A) PM-3112-240P-CPS: CTØ24 mm (0.15 A ~ 200 A) |
| Input Frequency | 50/60 Hz |
| W Accuracy | Better than 0.5% (PF=1) |
| Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency |
| Data Update Rate | 1 Second |
| Relay Output | |
| Channels | 2 |
| Type | Power Relay |
| Contact Rating | Form A: 5 A @ 250 VAC 5 A @ 30 VDC |
| CANopen | |
| Baud Rate | 125 k (default), 250 k, 500 k, 1 M; DIP Switch Selectable |
| Protocol | CANopen |
| Power | |
| Input Range | +12 ~ 48 VDC |
| Consumption | 2W |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 33 x 127 x 100 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -20 ~ +70 °C |
| Storage Temperature | -25 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Spesifikasjoner som oppgitt av produsenten. Med forbehold om endringer.
Nedlastinger
Logg inn