M-7016D-G Strain Gauge Input Module, 2-ch 4-wire, DCON and Modbus RTU
RS-485 strain gauge input module with two 4-wire full-bridge channels, 16-bit resolution, LED display and linear mapping for direct conversion of readings into weight.
- Two 4-wire full-bridge strain gauge inputs with 16-bit resolution
- Programmable input ranges from ±15 mV to ±2.5 V, plus ±20 mA current input
- Linear mapping function converts readings into engineering units through a user-defined table
- Excitation voltage output of 0 ~ +10 V with 40 mA maximum load current
- 1 digital input with 50 Hz event counter and 4 open-collector outputs with high/low alarm option
- RS-485 port supporting Modbus RTU and DCON, configurable via software
3 168,49 kr per stk.
| 1–9 stk. | 3 168,49 kr | |
|---|---|---|
| 10–30 stk. | 3 075,00 kr | −3 % |
| 31+ stk. | 3 012,67 kr | −5 % |
Produktinformasjon "M-7016D-G Strain Gauge Input Module, 2-ch 4-wire, DCON and Modbus RTU"
M-7016D-G is an RS-485 remote I/O module for converting the electrical output of strain gauges and load cells into measurable values. Two full-bridge, 4-wire analog input channels are each configurable for a range from ±15 mV to ±2.5 V or ±20 mA, with 16-bit resolution.
A user-defined linear mapping table lets the module return readings already scaled to engineering units, such as weight, without external conversion. An excitation voltage output of 0 ~ +10 V at up to 40 mA powers the sensor bridge, and the module adds one digital input with a 50 Hz event counter and four open-collector digital outputs that can be set as high or low alarms.
Configuration is carried out over RS-485 using Modbus RTU or DCON, with baud rates from 1200 to 115200 bps. The module carries a 5-digit 7-segment LED display, built-in dual watchdog and DIN-rail mounting, making it suited to building, factory and machine automation.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Strain gauge input module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus RTU |
| Digital inputs: | 1 |
| Digital outputs: | 4 |
| Analog inputs: | 2 |
| Analog outputs: | 1 |
| Ports: | 1 |
| Isolation: | 1500 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Spesifikasjoner
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Display | |
| Type | 5-Digit 7 Segment LED Display |
| Isolation | |
| Intra-module Isolation | 1500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Digital Input/Counter | |
| Channels | 1 |
| Type | Dry Contact |
| Sink/Source (NPN/PNP) | Source |
| ON Voltage Level | Close to GND |
| OFF Voltage Level | Open |
| Max. Counts | 65535 (16-bit) |
| Frequency | 50 Hz |
| Input Impedance | 3 kΩ |
| Overvoltage Protection | ±30 VDC |
| Digital Output | |
| Channels | 4 |
| Type | Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +3.5 ~ +50 VDC |
| Load Current | 30 mA/Channel |
| Power on Value | Programmable |
| Safe Value | Programmable |
| Strain Gauge, Load Cell Input | |
| Channels | 2 |
| Type | Full-Bridge Strain Gauge Voltage Current |
| Range | Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current: ±20 mA |
| Wiring | 4-wire |
| Accuracy | ±0.05% of FSR |
| Resolution | 16-bit |
| Sampling Rate | 1-ch Mode: 10 Hz 2-ch Mode: 2 Hz (total) |
| Impedance | 20 MΩ |
| Overvoltage Protection | ±5 VDC |
| Excitation Voltage Output | |
| Channels | 1 |
| Range | 0 ~ +10 V |
| Resolution | 16-bit |
| Accuracy | ±0.05% of FSR |
| Max. Load Current | 40 mA |
| Power on Value | Programmable |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
| Protocol | Modbus RTU, DCON |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 3.0 W |
| Mechanical | |
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Spesifikasjoner som oppgitt av produsenten. Med forbehold om endringer.