I-2533CS-B CAN to Single-mode Fiber Bridge, 15 km, SC Connector, 1550/1310 nm
CAN to single-mode fibre bridge that extends a CAN bus link up to 15 km at any CAN baud rate over one SC fibre. Supplied as one half of a pair with the I-2533CS-A.
- Single-mode SC fibre link of up to 15 km at any CAN baud rate
- Bidirectional CAN data over one fibre using WDM, TX 1550 nm and RX 1310 nm
- 2500 Vrms isolation on the CAN side
- Supports CAN 2.0A and CAN 2.0B, fully compatible with ISO 11898-2, NXP TJA1042 transceiver
- Rotary switch or user-defined CAN baud rate from 10 k to 1 M bps
- Fibre broken line detection and utility tool for CAN message filter configuration
2 815,28 kr per stk.
| 1–9 stk. | 2 815,28 kr | |
|---|---|---|
| 10–30 stk. | 2 732,18 kr | −3 % |
| 31+ stk. | 2 669,84 kr | −5 % |
Produktinformasjon "I-2533CS-B CAN to Single-mode Fiber Bridge, 15 km, SC Connector, 1550/1310 nm"
The I-2533CS-B is a local CAN bridge that connects a CAN bus segment to a single-mode fibre link, allowing two CAN networks to communicate across distances of up to 15 km. Wavelength division multiplexing carries bidirectional CAN data over a single SC fibre, which reduces the amount of fibre cable needed for the installation.
The I-2533CS-B must be used together with the I-2533CS-A, as the two units are a matched pair due to hardware limitations, so both must be purchased. The link distance does not depend on the CAN baud rate, and the two networks can run at different baud rates. A bus error on one CAN network does not affect the other, and the fibre link includes broken line detection.
Configuration is handled by a rotary switch for standard baud rates or a user-defined rate between 10 k and 1 M bps, an on-board switch for the 120 Ω terminal resistor, and a utility tool for CAN message filter setup through the RS-232 utility port. The unit mounts on DIN-rail and has a removable terminal block.
Applications
- Extending CAN bus networks over long distances using single-mode fibre
- Linking two CAN bus systems that run at different baud rates
- Isolating a CAN network so that bus errors on one side do not affect the other
- Control and monitoring installations in various industries
| Product type: | CAN to Fiber Bridge |
|---|---|
| Interface: | CAN, SC single-mode fibre |
| Protocol: | CAN 2.0A, CAN 2.0B |
| Ports: | 1 CAN, 1 fibre (SC) |
| Isolation: | 2500 Vrms (CAN side) |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Plastic |
Spesifikasjoner
| LED Indicators | |
|---|---|
| Status | 1 x Power 3 x CAN status 2 x Fiber status |
| COM Ports | |
| Ports | 1 x RS-232 (Utility Port) |
| Fiber | |
| Ports | Single-Mode; SC connector x 1; 100 Base-FX |
| Fiber Cable | 8.3/125, 8.7/125, 9/125 or 10/125 μm |
| Wavelength | TX: 1550, RX: 1310 nm |
| TX Output | -14 dBm Min. , -8 dBm Max. |
| Transmission Distance | 15 km (9/125 μm recommended) |
| RX Sensitivity | -31 dBm Max. |
| RX Overload | -5 dBm Max. |
| Budget | 17 dBm |
| Propagation Delay | 190 us (*Note2) |
| CAN | |
| Ports | 1 |
| Specification | ISO 11898-2, CAN 2.0A and CAN 2.0B |
| Baud Rate | 10 k ~ 1 M bps |
| Isolation | 2500 Vrms on the CAN side |
| Terminal Resistor | Switch for 120Ω terminal resistor |
| Filter | Yes |
| Power | |
| Input Range | +10 VDC ~ +30 VDC |
| Consumption | 3 W |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 33.0 x 126 x 101 (W x L x H) |
| Installation | DIN-Rail |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Spesifikasjoner som oppgitt av produsenten. Med forbehold om endringer.