DL-100TM485S IP66 Temperature & Humidity Data Logger, RS-485 Modbus RTU
IP66 remote temperature and humidity data logger with LCD display, RS-485 interface and Modbus RTU protocol. Stores up to 4088 records across a -20 to +60 °C range.
- Measures -20 to +60 °C and 0 to 100% RH with 0.1 °C and 0.1% resolution
- Typical accuracy ±0.4 °C and ±3% RH (non-P version)
- Stores up to 4088 temperature and humidity records, with overwrite or stop-when-full modes
- Logging interval adjustable from 10 seconds to 1 day
- RS-485 interface with Modbus RTU at 1200 to 115200 bps
- LCD display for temperature, humidity and module ID
1 277,79 kr per stk.
| 1–9 stk. | 1 277,79 kr | |
|---|---|---|
| 10–30 stk. | 1 236,23 kr | −3 % |
| 31+ stk. | 1 215,45 kr | −5 % |
Produktinformasjon "DL-100TM485S IP66 Temperature & Humidity Data Logger, RS-485 Modbus RTU"
DL-100TM485S is a black-cover, IP66 remote data logger for monitoring temperature and relative humidity over a -20 to +60 °C and 0 to 100% RH measurement range. Readings are stored internally, shown on an LCD and made available over RS-485 using Modbus RTU, so the module can feed a supervisory system or be read on site.
This non-P version has a typical accuracy of ±0.4 °C and ±3% RH between 20 and 80% RH. Logging intervals run from 10 seconds to 1 day, and when storage is full the module can either overwrite older records or stop logging, as configured.
Configuration, retrieval and charting are handled with the DL Utility, which can export data to Excel. The unit runs from 10 to 30 VDC, mounts on a DIN-rail or wall, and is rated IP66 for harsh or washdown environments.
Applications
- Transportation of food or pharmaceuticals
- Food and beverage industry (HACCP)
- Blood stations and pharmacies
- Building and energy management
- Warehouses
- Museums, archives and galleries
| Product type: | Data Logger |
|---|---|
| Interface: | RS-485 |
| Protocol: | Modbus RTU |
| Ports: | 1 |
| Isolation: | Non-isolated |
| Power input: | 10 to 30 VDC |
| Operating temperature: | -20 ~ +60 °C |
| Mounting: | DIN-rail, wall mount |
| Housing: | IP66 |
Spesifikasjoner
| Data Logger | |
|---|---|
| Mode | Overwrite or stop logging when storage space is full |
| Time Interval | 10 seconds to 1 day |
| Overwrite Limitation | 1,000,000 cycles |
| Max. Records | 4088 temperature and humidity records |
| Display | |
| LCD Information Displayed | Temperature (°C and °F), Humidity (RH), Module ID |
| Temperature Measurement | |
| Range | -20 to +60 °C (-4 to +140 °F) |
| Resolution | 0.1 °C |
| Accuracy | Typical: ±0.4 °C |
| Humidity Measurement | |
| Range | 0 to 100% RH |
| Resolution | 0.1% |
| Accuracy | Typical: ±3% RH @ 20 to 80% RH |
| Dew Point | |
| Range | Calculated using temperature and relative humidity |
| Resolution | 0.1 °C |
| COM Ports | |
| Ports | 1 x RS-485, Non-isolated |
| Baud Rate | 1200 to 115200 bps |
| Data Format | (N, 8, 1) |
| Protocol | Modbus RTU |
| Power | |
| Input Range | +10 to +30 VDC |
| Consumption | 0.15 W |
| Mechanical | |
| Dimensions (mm) | 82 x 172 x 55 (W x L x H) |
| Installation | DIN-Rail; Wall mount |
| Ingress Protection Rating | IP66 |
| Cable Length | 380 mm |
| Environment | |
| Operating Temperature | -20 to +60 °C |
| Storage Temperature | -30 to +80 °C |
| Humidity | 5 to 95% RH, Non-condensing |
Spesifikasjoner som oppgitt av produsenten. Med forbehold om endringer.