CL-203-WF IAQ Data Logger, CO/CO2/Temperature/Humidity, Wi-Fi and PoE
IAQ data logger module measuring CO, CO2, temperature, humidity and dew point, with RS-485, Ethernet PoE and Wi-Fi interfaces. Stores up to 450,000 time-stamped records.
- Measures CO (electrochemical, 0 to 1000 ppm), CO2 (NDIR, 0 to 9999 ppm), temperature and humidity, and calculates dew point
- Stores up to 450,000 records with date and time stamps for download and export
- RS-485, Ethernet and IEEE 802.11 b/g/n Wi-Fi interfaces
- DCON, Modbus RTU and Modbus TCP support, plus MQTT on the Ethernet interface
- One Form A relay output for alarm or IAQ device control
- Redundant power via PoE (IEEE 802.3af, Class 1) or +12 ~ +48 VDC terminal block
4 830,65 kr per stk.
| 1–9 stk. | 4 830,65 kr | |
|---|---|---|
| 10–30 stk. | 4 685,21 kr | −3 % |
| 31+ stk. | 4 591,72 kr | −5 % |
Produktinformasjon "CL-203-WF IAQ Data Logger, CO/CO2/Temperature/Humidity, Wi-Fi and PoE"
CL-203-WF CR is an indoor air quality monitoring module that logs carbon monoxide, carbon dioxide, temperature, humidity and dew point. Each reading is stored with date and time stamps, and up to 450,000 records can be downloaded later.
Connectivity covers RS-485, Ethernet and Wi-Fi, so the module can feed existing HMI or SCADA systems over DCON, Modbus RTU or Modbus TCP. Where Ethernet is used, MQTT is also available. The relay output can drive an alarm or control IAQ equipment directly.
Real-time readings can be viewed from the supplied utility or the iOS and Android apps when the device is on the same local network. Power can come from PoE or a DC terminal block, and the unit mounts on a ceiling or wall.
Applications
- Transportation of food or pharmaceuticals
- Food and beverage industry (HACCP)
- Blood stations and pharmacies
- Building and energy management
- Warehouse management
- Museums, archives and galleries
- Indoor or underground parking lot air quality monitoring
| Product type: | Data logger module |
|---|---|
| Interface: | Ethernet, RS-485, Wi-Fi |
| Protocol: | DCON, Modbus RTU, Modbus TCP, MQTT |
| Relay outputs: | 1 x Form A |
| Ports: | 2 |
| PoE: | IEEE 802.3af, Class 1 |
| Power input: | +12 ~ +48 VDC, PoE |
| Operating temperature: | 0 ~ 50°C |
| Mounting: | Ceiling, wall |
Spesifikasjoner
| CPU Module | |
|---|---|
| Watchdog Timer | Yes, Module (2.3 seconds), Communication (Programmable) |
| System | |
| Security | IP filter (whitelist) and Password (web) |
| Alarm | CO/CO2/RH/Temperature |
| Real Time Clock | Yes |
| Data Logger | Yes, up to 450,000 records |
| Temperature Measurement | |
| Range | -10 ~ +50°C |
| Resolution | 0.1°C |
| Accuracy | ±0.6°C |
| Humidity Measurement | |
| Range | 0 ~ 100% RH, Non-condensing |
| Resolution | 0.1% RH, Non-condensing |
| Accuracy | ±5% RH, Non-condensing |
| CO Measurement | |
| Range | 0 to 1000 ppm (Electrochemical) |
| Resolution | 1 ppm |
| Accuracy | ±5% of measured value |
| Response Time | 30 seconds |
| Warm-up Time | 5 minutes |
| CO2 Measurement | |
| Range | 0 to 9999 ppm (NDIR) |
| Resolution | 1 ppm |
| Accuracy | ±40 ppm ±3% of measured value |
| Response Time | 120 seconds |
| Warm-up Time | 5 minutes |
| Wi-Fi | |
| Transmission Distance (LoS) | 50 meters (LOS) |
| Standard Supported | IEEE 802.11 b/g/n |
| RX Sensitivity | -95.7 dBm @ 1 DSSS, -74.0 dBm @ 54 OFDM |
| Output Power | 18 dBm @ 1 DSSS, 14.5 dBm @ 54 OFDM |
| Mode | Infrastructure & Limited AP |
| Encryption | WEP, WPA and WPA2 |
| Antenna | 1 dBi (PCB Antenna) |
| Relay Output | |
| Channels | 1 x Form A, SPST 30 VDC @ 16 A or 250 VAC @ 16 A |
| Ethernet | |
| Ports | 10/100 Base-TX, 8-Pin RJ-45 x1 (Auto-negotiating, Auto-MDI/MDIX, LED indicators) |
| COM Ports | |
| Ports | 1 x RS-485 1 x Ethernet |
| Baud Rate | 1200 ~ 115200 bps |
| Protocol | DCON and Modbus/RTU (RS-485) Modbus TCP (Ethernet, Wi-Fi) MQTT (Ethernet) |
| Power | |
| Consumption | Non-PoE: 1.7 W (Max.) PoE: 1.8 W (Max.) |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
| Dimensions (mm) | Ø 150 x 53 (Ø x H) |
| Installation | Ceiling Mounting/Wall Mounting |
| Ingress Protection Rating | IP20 |
| Environment | |
| Operating Temperature | 0 ~ 50°C |
| Storage Temperature | -30 ~ +75°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Spesifikasjoner som oppgitt av produsenten. Med forbehold om endringer.